Providing service to users of equipment such as Electron Microscopes, Steppers, Scanners, Lasers or any other equipment with Vibration, Magnetic field or acoustic sensitivities.

Home 831-465-9189
Home • Up • Services • Monitoring • Cancellation • Spectrum Analyzer • Profile • Projects • Design • Sample Reports • Customers • Contact us


Site Selection Considerations For Scanning and Transmission Electron Microscopes

Wayne Vogen
Vibration Engineering Consultants, Inc.
Santa Cruz, California


Go directly to the section on VibrationGo directly to the section on AcousticsGo directly to the section on Fields

 

Environmental factors must be controlled including floor vibration, acoustic level and magnetic field when choosing a site for an electron microscope. A systematic procedure for selecting a site from possible candidates is presented in this paper.

The best way to assure that the floor vibration is low is to locate the microscope on the ground. The ground vibration level is rarely too high, If it is too high the vibration sources can easily be identified and eliminated. In addition, vibration isolation tables will not be required if the microscope is located on the ground. No single factor is as important as finding a suitable location at ground level.

Many clean rooms have raised floors above the ground to provide room for various utilities and airflow. For this case it is desirable to provide a platform that does not increase the vibration level of the ground and is usually called a gravity table. These tables can be purchased from isolation table manufacturers or built with certain simple guidelines. A steel table with bolted, rather than welded construction is preferred. The bolted construction provides higher damping because of the friction in the joints that result in lower motion amplification at the table resonant frequencies. In addition a bolted table can be assembled in pieces that eases the placement in the clean room. The legs of the table should be located under the feet of the instrument so that the diaphragmatic resonant modes of the tabletop do not increase the vibration level at the feet of the instrument. Adequate cross bracing is essential to assure that the lateral bending modes of the table and instrument combination are high enough in frequency so as not to degrade performance. Figure I presents a design for a gravity table for a one kilogram SEM that has proven to be quite acceptable. This table design can be scaled easily to fit individual requirements. Leave adequate space (1 cm.) between the floor tiles and the table to prevent foot fall vibration from affecting performance of the microscope.

If a location on the ground is impossible to accommodate, no site should be selected without a site survey that measures floor vibration, acoustic level and magnetic fields. A site survey prevents expensive situations in which the electron microscope either needs to be relocated, the site rectified, a vibration isolation table or acoustic enclosure purchased and installed or reduced performance tolerated. In addition, most solutions to an undesirable site are expensive, time consuming and usually less optimum then selecting a good location originally.

When the vibration level is too high the typical reaction is to specify a vibration isolation table. Example of Steel Equipment PedestalHowever, isolation tables have their own set of problems. They amplify the ambient vibration at low frequencies and can interact with the existing isolation system of the electron microscope and the floor resonance's and building modes of vibration to produce unwanted performance. In a clean room the value of the additional area required for the table often exceeds the cost of the table. The tables need to be maintained; our experience shows that over half the existing vibration isolation tables are not working correctly because of various reasons. Some of the reasons include 1. the table is not needed so it is not activated, 2. it is adjusted incorrectly, 3. some miscreant has played with the air supply or leveling system, 4. or it is broken. Usually the user is unaware that the isolation table is not working correctly.

If a vibration isolation table is being considered, expert advice should be obtained and a floor vibration survey should be made to assure that the table will provide the desired performance.

High acoustic levels ( >75 dB(C) ) can degrade performance of electron microscopes and high performance steppers. Acoustic degradation of machine performance has become as important as floor vibration. The high air flow common in modern clean rooms and the reduced line width of semiconductors have combined to make acoustic excitation an important consideration when selecting a site for electron microscopes and steppers. Generally one must consider acoustic levels when the semiconductor process is producing features smaller than 1.3 microns. Floor vibration isolation systems can increase the sensitivity to acoustic excitation because the large mass of the instrument is no longer anchored to the large mass of the floor because it is separated by the soft springs of the isolation system.

How can acoustic excitation be controlled? First, when a clean room is being designed, inlet and outlet attenuators should be installed on all HVAC fans. The attenuators can be ordered from commercial HVAC equipment suppliers. They are relatively inexpensive, simple and cause little pressure drop. Clean rooms fitted with this equipment should have noise levels below 72 dB(C). If the clean room is constructed without attenuators, space should be left to accommodate them if the desire arises later. Most existing clean rooms cannot be retrofitted economically with attenuators. Sometimes sound absorbing material can be added in the plenum and ducts up stream of the HEPA filters. However, the sound absorbing material will increase the particulate load on the filters and shorten their life. our experience has shown that a 5-6 dB(C) noise reduction is typical for this type of solution.

Another solution is a sound attenuating enclosure fitted with a separate HEPA filter system, VEC and Industrial Acoustics Corporation have developed a system that can isolate individual pieces of equipment in a clean room. These systems are medium priced and somewhat inconvenient; for instance the SEM operator has to open a door to change apertures, insert a sample, etc. However if a high

sensitivity electron microscope has to be located in a high noise room, this is a viable solution.

If small rooms have high noise levels because of fans, low noise fans can be substituted for existing equipment such as axial flow, plug fans. HVAC suppliers can provide the correct solution.

Finally, active cancellation of acoustic noise in air ducts can solve selected acoustic problems where the unwanted noise propagates in an air duct. This is usually not a practical solution in a clean room because of the high number of fans and ducts and most rooms are connected by a common plenum.

Electric currents cause magnetic fields that can interfere with the performance of the electron microscope. Generally, the fields should be measured since their presence is usually not obvious. These fields can be minimized by simple design and construction techniques. Following these rules during construction and design usually involves very little extra cost. in this paper we will address EMI below one kilohertz.

One of the major sources of EMI disturbances is power distribution wires that are usually in conduits. This is almost always caused by either a fault condition or high amounts of current in the conductors. In a normal conduit with a hot and neutral wire the currents should be equal and opposite, and the magnetic fields from the two wires should cancel. If high net currents from the conduit are measured with a current meter, either the hot and neutral currents are not equal (usually caused by loss of the neutral current) or the conduit itself is carrying significant current. In either case this represents a fault (and possible safety) condition and should be corrected.

In order to cancel the external field totally the wires would have to be coaxial. This is not common with current carrying wires so a net external field is present because of the separation of the wires. This field can be minimized by twisting the current carrying wires in the conduit. This is not standard practice but should be done in new installations. In addition some problems have been corrected by twisting wires in existing conduits that had external fields when the currents were balanced. It the conduit shows a significant current when measured with a current meter and the currents in the hot and neutral are equal, the steel conduit is probably carrying the current. Again, this is a fault condition that should be identified and corrected.

A common EMI problem is caused by significant ground currents in water pipes, gas pipes, rebar or metal wall studs. This situation is caused by normal grounding procedures. The problem is extremely difficult to isolate and correct. If the current carrier is identified sometimes it is possible to eliminate by breaking the current path with a dielectric material, for instance by installing a dielectric union in a copper pipe. More often the current finds a new path and remains a problem. Many times the only practical solution is to move the pipe or electron microscope.

For currents below one kilohertz the only effective shield is a magnetically permeable material. The most effective and expensive metal is mu metal. Iron or steel is quite practical and less expensive. The iron conduit reduces the field from the wires roughly 3 to 5 times. If maximum shielding is desired, specify the heaviest wall conduit.

Generally, the goal is to produce a room with fields lower than 1 milligauss. It is not effective to try to shield whole rooms because the initial permeability of mu metal or iron is higher than a few mGauss and limit its success. If shielding is indicated it is more practical to identify and shield the source because the field is high enough at the source to over come the initial permeability of the material. For instance, if a welder is a source of high fields a box of 1/8 inch thick, hot rolled steel will strongly attenuate the fields. The larger the box, the less effective it will be.

High current carrying conduits should be routed away from EMI sensitive equipment. Care should be taken to route the conduit supplying the power to the EMI sensitive equipment in as direct a manner as possible. Do not route the power in a loop around the equipment. This sometimes happens when modular power lines are installed in the laboratory.

The magnetic field decreases with distance. The reduction varies with the distance from a line source (a straight wire), the distance squared from a dipolar source (two separated wires with opposite currents) and at least the distance squared from a transformer or heater. Obviously placing the sensitive equipment as far from the magnetic source as possible is beneficial.

Florescent lights can be a source of strong EMI. The magnetic fields are produced by some types of ballast in the light fixture. This problem can be fixed by using low magnetic field producing ballasts or incandescent lights.

Cathode ray tubes or monitors are major sources of EMI. The horizontal scan coils are the primary source of the EMI. The affect on the electron microscope can be detected by measuring the spectrum of the magnetic field, or by turning the monitor off. The scan frequency is usually different from the 60-hertz line frequency. Beware of "low EMI" emitting monitors since most of them direct the magnetic fields out the side of the monitor instead of the front where the personnel is usually located. Usually the problem is corrected by moving the monitor farther away from the column of the electron microscope. 

 

Vibration Engineering Consultants, 4555 Paul Sweet Road, Santa Cruz, CA 95065,   (831) 465-9189